GE Multilin C60 Breaker Protection System B-45
APPENDIX B B.4 MEMORY MAPPING
B
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00 Neutral Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F01 Neutral Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F02 Neutral Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7F03 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F04 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F05 Neutral Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7F07 Neutral Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F08 Neutral Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F09 Neutral Overvoltage 1 Curves 0 to 3 --- 1 F116 0 (Definite Time)
7F0A Reserved (7 items) 0 to 65535 --- 1 F001 0
7F11 ...Repeated for Neutral Overvoltage 2
7F22 ...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (2 modules)
7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 700
7F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7F66 Auxiliary Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7F68 Auxiliary Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F69 Auxiliary Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F6A Reserved (7 items) 0 to 65535 --- 1 F001 0
7F71 ...Repeated for Auxiliary Undervoltage 2
Auxiliary Overvoltage (Read/Write Grouped Setting) (2 modules)
7FA0 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7FA1 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7FA2 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7FA3 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7FA4 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7FA5 Auxiliary Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7FA7 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7FA8 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7FA9 Reserved (8 items) 0 to 65535 --- 1 F001 0
7FB1 ...Repeated for Auxiliary Overvoltage 2
Frequency (Read Only)
8000 Tracking Frequency 2 to 90 Hz 0.01 F001 0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0 Reserved Register T1 -55 to 125 C 1 F002 -55
81C1 Reserved Register T2 -55 to 125 C 1 F002 125
81C2 Reserved Register T3 -2147483647 to
2147483647
--- 1 F004 0
81C4 Reserved Register T4 0 to 4294967295 --- 1 F003 0
81C6 Reserved Register T5 0 to 4294967295 --- 1 F003 0
81C8 Reserved Register T6 0 to 4294967295 --- 1 F003 0
81CA Reserved Register T7 0 to 4294967295 --- 1 F003 0
81CC Reserved Register T8 0 to 4294967295 --- 1 F003 0
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0 EGD Fast Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0
83E1 EGD Fast Producer Exchange 1 Configuration Time 0 to 4294967295 --- --- F003 0
83E3 EGD Fast Producer Exchange 1 Size 0 to 65535 --- 1 F001 0
EGD Slow Production Status (Read Only Non-Volatile and Read Only) (2 modules)
83F0 EGD Slow Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT