Rectifier Utility data screen
This screen refers to the AC source supplying the Rectifier.
This screen displays:
Iout1 = output current Rectifier Bridge.
Iout2 = output current 2
nd
Rectifier Bridge (optional 12 pulse Rectifiers only).
The voltage levels between the three phases (line-to-line).
The input frequency of the Rectifier.
RECTIFIER
U12=481V Iout1 =592A
U23=480V Iout2 = 0A
U31=482V f=60.0Hz
metering
alarms
parameters
+
ok
Inverter data screen
This screen displays:
The voltage level of the three phase voltages (line-to-neutral).
The output frequency of the Inverter.
The synchronization status of the Inverter with respect to Utility.
INVERTER: U1=277V
U2= 277V U3=277V
Frequency = 60.0Hz
Synchronized
metering
alarms
parameters
+
ok
Status Load screen
This screen displays:
The Load level in kVA (for RPA: only this unit).
The Load level as a percentage of the nominal rated Load (for RPA: only this unit).
The source of the power supplied to the Load.
LOAD ON UPS
Load = 399.44kVA
Percentage = 80%
LOAD ON INVERTER
metering
alarms
parameters
+
ok
Load on phases screen 1
This screen displays for each phase:
The output phase voltage and current as RMS values (for RPA: total value of Parallel System).
The output Load as percent (for RPA: respect to the rated power of Parallel System).
LOAD ON PHASES
U1=277V I=505A 84%
U2=277V I=475A 79%
U3=277V I=462A 77%
metering
alarms
parameters
+
ok