OPM_SGS_USM_M40_M50_1US_V020.doc Operating Manual SG Series 400 & 500 kVA
3. Disconnect the Battery from all Units (only for UPS configuration without external
Battery Breaker Release).
Wait 5 minutes for DC-Link Capacitors to discharge.
Before you proceed with any kind of
intervention on the UPS, make sure the DC-Link
voltage be less than 15 VDC.
Ub=15V
Ib= + 0A
Battery Temp= + 20
°
C
Charge Level= 87%
Autonomy = 12min
metering
alarms
parameters
+
ok
First operated unit All other units of the system
4. Disconnect the Utility supply from all Units.
All LED’s are OFF.
First operated unit All other units of the system
END OF PROCEDURE