DEH-41304C EntelliGuard® G Circuit Breaker
13 March 14 Section 6 – Accessories Description
©2012 General Electric All Rights Reserved 27
SECTION 6 – ACCESSORIES DESCRIPTION
IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate, service
and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.
GENERAL INFORMATION
A wide range of optional accessories are interchangeable
across all EntelliGuard G power circuit breakers, regardless
of nominal rating or envelope/frame size. Each accessory
incorporates easy-fit design features for quick installation,
either at the factory or in the field (Fig. 6.1).
NOTE: Replacement accessories have an “R” at the end of
the catalog number as shown.
Figure 6.1. Accessory Mounting
INDIVIDUAL ACCESSORIES
Motorized Spring Charging Unit
The unique motor/gearbox unit is specially designed to
operate with the full range of EntelliGuard G. It is easily
fitted with three heavy-duty bolts. After a breaker close
operation, the unit automatically recharges the spring and
makes it ready for immediate open and re-close should the
need arise. High speed recharging ensures that the springs
are fully charged within approximately three seconds
following a release. All electrically operated (EO) ANSI/UL
breakers are equipped with “Spring Charged” contacts
(GSCC1R) for status indication (Table 6.1).
Table 6.1 Motor Operators
Spring charge contact is power rated only, as shown below.
Spring charge time = 3 sec max.
Recommended fuse amps: contact factory.
Duty cycle = 2/min.
Envelope 1 motors: running VA ~ 300 VA; inrush = 2 to 3 times.