EntelliGuard® G Circuit Breaker DEH-41304C
Section 6 – Accessories Description 13 March 14
30 ©2012 General Electric All Rights Reserved
Circuit Breaker - Key Interlock Facility
This option provides factory-installed interlocking devices for
installation between separate circuit breakers (baseplates and
mechanism). This safeguard ensures that a circuit breaker
cannot be closed unless the dedicated key has been inserted
and secured within the lock. Circuit breakers accept ready-to-fit
interlocking device kits such as Castell, Ronis, Kirk and Profalux
for installation between related, separate circuit breakers (Table
6.10).
NOTE: Locks and keys are not supplied by GE. Please order
separately from your local supplier.
Table 6.10. Key Interlocks and Door Interlocks
Baseplate and mechanism for Ronis locks
(breaker mounted)
Baseplate and mechanism for Kirk Key locks
(breaker mounted) (Question on markup.)
Mechanism for Ronis key cassette interlock
(cassette mounted)
Mechanism for Kirk key cassette interlock
(cassette mounted)
Door interlock (left side)
Door interlock (right side)
Carriage Position Switch (TOC)
Available as an option for mounting within the base of the
cassette/substructure, the carriage position switch provides
six single-pole changeover contacts for local or remote
electrical indication of the circuit breaker status:
CONNECTED, TEST and DISCONNECTED. The DISCONNECTED
position is indicated only when minimum isolating distances
between contacts on both the main and auxiliary circuits
have been achieved. This option is in addition to the
mechanical indicators, which are fitted as standard. When
installed, the carriage switch is IP2X protected and includes
wiring to a terminal block located on the left side of the
cassette (Tables 6.11 and 6.12).
Table 6.11. Carriage Position Switches
1 NO/NC switch per position
Set of 2 No/NC switches per position
Table 6.12. Carriage Position Switch Ratings (Common
NO/NC Contact Configuration)
Mechanical Interlocks (Cable/Rod)
Available for fixed and drawout circuit breakers, these units
enable the direct interlocking of EntelliGuard G circuit
breakers, either mounted side-by-side or stacked. The
interlocking mechanisms are connected by a specially designed
cable or rod in a 1 from 2, 1 from 3, and 2 from 3
configuration, and any mix of current ratings/pole
configurations can be accommodated. Standard cable lengths
available: 1.0 m, 1.6 m, 2.0 m, 2.5 m, 3.0 m, 3.5 m and 4.0 m.
(Please contact our technical customer service department if
longer length is required.)
Mechanical interlocks can be fitted to electrical systems as
shown in Table 6.13 and can link 2 and/or 3 circuit
breakers. Any nominal rating, frame size, number of poles
or type (fixed pattern or draw-out) can be interlocked
(Tables 6.13 and 6.14).
Table 6.13. Mechanical Interlocks (Cable/Rod)
Number of
Cables
Required
Contact factory for availability.
Cables
Standard cable lengths are shown in Table 6.14. (Cables
ordered separately. Please contact our technical customer
service department if longer length is required.)
Table 6.14. Cables for Mechanical Interlocks
Contact factory for availability.