DEH-41304C EntelliGuard® G Circuit Breaker
13 March 14 Section 6 – Accessories Description
©2012 General Electric All Rights Reserved 29
Table 6.5. UVR Operating Characteristics
DC: 350 W,
20 W (sealed)
AC: 350 W
(inrush),
20 W (sealed)
ď‚· Duty cycle = 2/min.
ď‚· Inrush = 350 VA (ac), 350 W (dc).
ď‚· Holding = 60 VA (ac), 50 W (dc).
Time Delay Module (TDM) for UVR (Externally Mounted)
The de-energized operation of the Under Voltage release can
be delayed. This optional, externally mounted module has an
adjustable time delay of 0 s to 3 s. The device can be
implemented to prevent undesired breaker tripping due to
momentary voltage interruptions and is connected in series
with the Under Voltage release. The time delay is in addition
to the time delay from the breaker mounted UVR accessory.
The time delay module starts counting at 50% of rated
voltage (Fig. 6.2 and Table 6.6).
Figure 6.2. Time Delay Module
Table 6.6 TDM Characteristics
Remote Operation Coil Combination
Each breaker accepts a maximum of four coils in the
combinations shown in Table 6.7. All coils are mounted from
the front and snap onto the mechanism after the fascia is
removed.
Table 6.7. Remote Operation Coil Combination
Coil Position on Fascia (from left)
Auxiliary Switches
Auxiliary switches indicate breaker main contact position.
They change their state in the same time sequence as the
breaker main contacts. See Tables 6.8 and 6.9 for available
combinations and ratings.
Table 6.8. Auxiliary Switches
Power rated (3NO+3NC) + low signal (Hi-Fi)
(2NO+2NC)
Power rated (4NO+4NC) + low signal (Hi-Fi)
(4NO+4NC)
Table 6.9. Auxiliary Switch Ratings and Secondary
Disconnect Points
Power rated (3NO+3NC) +
low signal (Hi-Fi)
(2NO+2NC)
A14 - A25,
B4 - B13,
B17 - B26
Power rated (4NO+4NC) +
low signal (Hi-Fi)
(4NO+4NC)*
A14 - A25,
B12 - B13,
B25 - B26
*Options are not available for side mounted sec disc blocks.
ď‚· High Fidelity refers to gold-plated contacts. Use for signal level outputs
(10 mA min to 100 mA max., 8 Vdc to 30 Vdc, 125 Vac.