GFK-2571A Chapter 5 Diagnostics 5-15
5
PROFINET Controller Faults in the RX3i Fault Tables
The PNC logs all (Local, Controller, I/O) faults in its Local Log. In addition, it logs Controller and I/O
faults in the corresponding RX3i CPU’s fault tables (the Controller Fault Table or the I/O Fault
Table).
Clearing the RX3i Fault Tables
Clearing one or both of the RX3i CPU’s fault tables has no effect on the PNC’s Local Log table.
The PNC’s Local Log can only be cleared from its Command Line Interface.
Clearing one or both of the RX3i CPU’s fault tables has no effect on the Diagnosis conditions
maintained by any IO-Device.
When the RX3i CPU’s fault tables are cleared, PROFINET-related faults are NOT re-reported,
even if the condition that is causing the fault still exists.