Infinity S (NE-S) Dual Voltage Power System Quick Start Guide
3
Document 8600243957P Rev 2 Jan 2019
GE
Critical Power
3
CAUTION: Verify battery voltage and polarity with a
voltmeter before connecting.
Distribution panels are each equipped with 20 (19” panel) or 26 (23” panel) bullet-style distribution positions. Each
position is selectable between Primary or Secondary (Converter) Voltage outputs.
Breaker sizes up to 250A, TPS fuses to 70A and GMT fuses to 12A are available.
Lug Landings
Distribution
Battery Bus
Landings
1/4-20 studs on 5/8centers
Lug tongue width 0.68” max
5/16-18 studs on 1” centers
Torque
65 in-lb - 7/16” socket
160 in-lb - 1/2” socket