Setpoints, Pg. 2 3 SETUP AND USE
Page Line Information Line Setpoint Range and Units Manual Ref.
3-21
2 1
PAGE 2: SETPOINT VALUESPAGE 2: SETPOINT VALUES
RTD SETPOINTSRTD SETPOINTS
2
RTD SENSOR TYPERTD SENSOR TYPE
TYPE = 100 OHM PLATINUMTYPE = 100 OHM PLATINUM
Not a setpoint.
Displays the RTD type the relay
will accept. To change the RTD
type, contact the factory.
100 ohm platinum, 10 ohm cop-
per, 100 ohm nickel, 120 ohm
nickel.
3.16
3
ARE THERE ANY RTDsARE THERE ANY RTDs
CONNECTED? XXXCONNECTED? XXX
YES or NO
When programmed to “NO”, all
RTD messages in Setpoints and
Actual Values are not displayed.
Factory Value = YES
3.16
4
RTD MESSAGE DISPLAY = CRTD MESSAGE DISPLAY = C
(C:CELSIUS/F:FAHRENHEIT)(C:CELSIUS/F:FAHRENHEIT)
C or F
Factory Value = C
3.16
5
# OF STATOR RTDS USED# OF STATOR RTDS USED
# OF RTDs = X# OF RTDs = X
0-6 (increments of 1)
Factory Value = 6
3.16
6
STATOR #1 ALARM LEVELSTATOR #1 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
or
RTD #1 ALARM LEVELRTD #1 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
0-200 degrees C or OFF
(increments of 1)
(32-392 degrees F)
Factory Value = OFF
3.16
7
STATOR #1 TRIP LEVELSTATOR #1 TRIP LEVEL
= XXX DEGREES C= XXX DEGREES C
or
RTD #1 TRIP LEVELRTD #1 TRIP LEVEL
= XXX DEGREES C= XXX DEGREES C
0-200 degrees C or OFF
(increments of 1)
(32-392 degrees F)
Factory Value = OFF
3.16
8
STATOR #2 ALARM LEVELSTATOR #2 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
or
RTD #2 ALARM LEVELRTD #2 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
0-200 degrees C or OFF
(increments of 1)
(32-392 degrees F)
3.16
9
STATOR #2 TRIP LEVELSTATOR #2 TRIP LEVEL
= XXX DEGREES C= XXX DEGREES C
or
RTD #2 TRIP LEVELRTD #2 TRIP LEVEL
= XXX DEGREES C= XXX DEGREES C
0-200 degrees C or OFF
(increments of 1)
(32-392 degrees F)
Factory Value = OFF
3.16
10
STATOR #3 ALARM LEVELSTATOR #3 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
or
RTD #3 ALARM LEVELRTD #3 ALARM LEVEL
= XXX DEGREES C= XXX DEGREES C
0-200 degrees C or OFF
(increments of 1)
(32-392 degrees F)
Factory Value = OFF
3.16