3 SETUP AND USE Setpoints, Pg. 5
3-30
19
MOTOR LOAD ANALOG OUTPUTMOTOR LOAD ANALOG OUTPUT
FULL SCALE = XXX %FLCFULL SCALE = XXX %FLC
This setpoint is used when the “Analog Output Parameter” setpoint is set to “MOTOR LOAD”. Motor load
as a percent of full scale can then be represented by the analog output signal.
25% – 250%, in increments of 1%.
Factory Value = 100%.
20
RELAY ALARMRELAY ALARM
LATCHCODE = XXLATCHCODE = XX
This setpoint allows the choice of output relay latch attributes. A latched output relay must be manually
reset. An unlatched relay will be automatically reset when the condition that caused the relay activation
goes away.
Note: Trip functions must always be manually reset regardless of the Latchcode value chosen
here. This setpoint allows Alarm functions to be either manually or automatically reset. The Immediate
O/L Alarm function will always be automatically reset regardless of the Latchcode.
latched = manual reset, unlatched = automatic reset
Value Trip Alarm Aux. 1 Aux. 2
1 latched unlatched unlatched latched
2 or 3 latched latched unlatched latched
4 or 5 latched unlatched latched latched
6 or 7 latched latched latched latched
Factory Value = 1
21
DRAWOUT FAILSAFE ACCESSDRAWOUT FAILSAFE ACCESS
CODE = 0 (See manual)CODE = 0 (See manual)
This setpoint appears only if the 269 is a drawout.
NOTE: FOR PROPER OPERATION OF A DRAWOUT UNIT, HARDWARE CHANGES MAY BE
REQUIRED IF THE FAILSAFE CODE IS CHANGED. (CONTACT FACTORY)
Entering value from factory for this setpoint allows access of the failsafe codes for approximately 3 min-
utes.
Factory Value = 0
• Messages are not displayed if the answer to the question “ARE THERE ANY RTDs CONNECTED?” is “NO”.
This setpoint is located on page 2 of setpoints, line 3.