EasyManua.ls Logo

GE Multilin F650 - Page 229

GE Multilin F650
259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-4 F650 Digital Bay Controller GEK-113000T
C.1 FACTORY DEFAULT SETTINGS APPENDIX C
C
PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Enable or disable the protocol
operation
Function DISABLED N/A [DISABLED – ENABLED]
Listening TCP port in the relay TCP Port 2404 N/A [0 : 65535]
Address in the ASDU header
Common Addr of
ASDU
255 N/A [0 : 65535]
Number of seconds for instantaneous
metering
Cyclic Meter Period 0 1 s [0 : 3600]
Not implemented Synchronization Event 0 N/A [0 : 3600]
IEC 870-5-104 NOTES
Note 1: Cyclic Meter Period 0 value means no spontaneous metering
PRODUCT SETUP>COMMUNICATION SETTINGS > SNTP
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Port used UDP port 123 1 [1 : 65535]
IP Address OCT 1 Server IP Oct 1 0 1 [1 : 255]
IP Address OCT 2 Server IP Oct 2 0 1 [1 : 255]
IP Address OCT 3 Server IP Oct 3 0 1 [1 : 255]
IP Address OCT 4 Server IP Oct 4 0 1 [1 : 255]
PRODUCT SETUP>COMMUNICATION SETTINGS >PROCOME
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Serial Remote Com Port selection COMM Port NONE [NONE – COM1]
Slave number for procome Slave Number 0 [0 : 254]

Table of Contents

Other manuals for GE Multilin F650