NX-8 Control
23
L LOCATION 37 - SIREN AND SYSTEM SUPERVISION (5 segments, feature selection data)
Location 37 is used to enable various system feature and reporting options. (Refer to the feature definitions.)
Segment 1: 1 - On if siren sounds for "Telephone Line Cut" when armed.
2 - On if siren sounds for "Telephone Line Cut" when disarmed.
3 - On if siren blast at arming.
4 - On if siren blast at exit expiration.
5 - On if siren blast at closing kissoff.
6 - On if siren sounds during a "Cross Zone" verification time.
7 - On if siren sounds for a Zone or Box Tamper.
8 - On if siren blasts 1 time for keyswitch or wireless arming; 2 times for disarming. (
NOTE: Must
be disabled for SIA CP-01 installations.
)
Segment 2: 1 - On if siren driver should be a voltage output. Off if on board siren driver enabled.
2 - On if siren sounds for expander trouble (Required for UL installations).
3 - On for Immediate Restore by zone. Off for zones to restore only when siren is off.
4 - On if Dynamic Battery Test performed at arming. Off if performed at disarming. (See loc 40)
5 - On if Battery Missing Test is performed every 12 seconds.
6 - On if Manual Bell Test performed during [r]-[4] test function.
7 - On if Manual Communicator Test performed during [r]- [4] test function.
8 - On if Box Tamper terminals on the control panel are enabled.
Segment 3: 1 - On if Box Tamper report enabled.
2 - On if AC Fail reporting enabled.
3 - On if Low Battery reporting enabled.
4 - On if Aux. Power Overcurrent report enabled.
5 - On if Siren Supervision report enabled.
6 - On if Telephone Line Cut report enabled.
7 - On if Ground Fault Detection report enabled.
8 - On if Expander Trouble reporting enabled.
Segment 4: 1 - On if Fail To Communicate report enabled.
2 - On if Log Full report enabled.
3 - On if Autotest report enabled.
4 - On if Start/End programming report enabled.
5 - On if End Download report enabled.
6 - On if Sensor Low Battery report enabled.
7 - On if Sensor Missing report enabled.
8 - Reserved.
Segment 5: 1 = On enable Lost Clock service light.
2 = On enables Zone Doubling (requires NX-200 Zone Doubling Kit).
3 = On disables On-Board 8 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = Reserved.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: Do NOT disable for UL listed systems
.
L LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips during an arming cycle that the NX-8 will allow before bypassing a zone. The
count determination is described in the feature definitions beginning on page 5. Factory default is 1.
.
L LOCATION 39 - KEYPAD SOUNDER CONTROL (1 segment, feature selection data)
Segment 1: 1 - On if keypad sounds for ATelephone Line Cut@ when the system is armed.
2 - On if keypad sounds for ATelephone Line Cut@ when disarmed.
3 - On if keypad sounds upon AC Power Failure.
4 - On if keypad sounds when a Low Battery is detected.
5 - On if keypad sounds during Cross Zone trip time.
6 - On if keypad sounds for zone and box tampers.
7 - Reserved.
8 - On if keypad sounds for expander trouble (required for UL installations).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NX-1308E - Caddx 8 Zone LED Keypad and is the answer not in the manual?

GE NX-1308E - Caddx 8 Zone LED Keypad Specifications

Power IconPower
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E power supply12 VDC Regulated 2 AMPS
LED keypad current draw130 mA max.
LED keypad zones normal w/o sounder55 mA
NX-148E LCD keypad current draw110 mA max.
NX-148E LCD keypad w/o sounder75 mA
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Loop Specifications IconLoop Specifications
standard loop resistance300 Ohms Maximum
2-wire smokes resistance30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Weight and Dimensions IconWeight and Dimensions
LED keypad width6.4"
LED keypad height4.0"
LED keypad depth1.1"
NX-148E LCD keypad width6.4"
NX-148E LCD keypad height5.3"
NX-148E LCD keypad depth1.0"
metal enclosure width11.25"
metal enclosure height11.25"
metal enclosure depth3.50"
shipping weight9 lbs.