NX-8 Control
37
LOCATION 129 - ZONE TYPE 10 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 130 - ZONE TYPE 11 ALARM EVENT CODE (1 segment, numerical data)
Location 130 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 130 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 131 - ZONE TYPE 11 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 132 - ZONE TYPE 12 ALARM EVENT CODE (1 segment, numerical data)
Location 132 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53.The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 132 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 133 - ZONE TYPE 12 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 134 - ZONE TYPE 13 ALARM EVENT CODE (1 segment, numerical data)
Location 134 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 134 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 135 - ZONE TYPE 13 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 136 - ZONE TYPE 14 ALARM EVENT CODE (1 segment, numerical data)
Location 136 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 136 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 137 - ZONE TYPE 14 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 138 - ZONE TYPE 15 ALARM EVENT CODE (1 segment, numerical data)
Location 138 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 138 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 139 - ZONE TYPE 15 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 140 - ZONE TYPE 16 ALARM EVENT CODE (1 segment, numerical data)
Location 140 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 140 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 141 - ZONE TYPE 16 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NX-1308E - Caddx 8 Zone LED Keypad and is the answer not in the manual?

GE NX-1308E - Caddx 8 Zone LED Keypad Specifications

Power IconPower
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E power supply12 VDC Regulated 2 AMPS
LED keypad current draw130 mA max.
LED keypad zones normal w/o sounder55 mA
NX-148E LCD keypad current draw110 mA max.
NX-148E LCD keypad w/o sounder75 mA
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Loop Specifications IconLoop Specifications
standard loop resistance300 Ohms Maximum
2-wire smokes resistance30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Weight and Dimensions IconWeight and Dimensions
LED keypad width6.4"
LED keypad height4.0"
LED keypad depth1.1"
NX-148E LCD keypad width6.4"
NX-148E LCD keypad height5.3"
NX-148E LCD keypad depth1.0"
metal enclosure width11.25"
metal enclosure height11.25"
metal enclosure depth3.50"
shipping weight9 lbs.