LOCATION 115 - ZONE TYPE 3 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 116 - ZONE TYPE 4 ALARM EVENT CODE (1 segment, numerical data)
Location 116 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2 the digit in location 116 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 117 - ZONE TYPE 4 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 118 - ZONE TYPE 5 ALARM EVENT CODE (1 segment, numerical data)
Location 118 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 118 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 119 - ZONE TYPE 5 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 120 - ZONE TYPE 6 ALARM EVENT CODE (1 segment, numerical data)
Location 120 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2 the digit in location 120 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 121 - ZONE TYPE 6 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 122 - ZONE TYPE 7 ALARM EVENT CODE (1 segment, numerical data)
Location 122 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53.The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 122 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 123 - ZONE TYPE 7 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 124 - ZONE TYPE 8 ALARM EVENT CODE (1 segment, numerical data)
Location 124 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 124 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 125 - ZONE TYPE 8 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 126 - ZONE TYPE 9 ALARM EVENT CODE (1 segment, numerical data)
Location 126 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 126 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.
LOCATION 127 - ZONE TYPE 9 CHARACTERISTIC SELECT (3 segments, feature selection data)
Use "Zone Type Characteristic Selections" described in Location 111, page 35.
LOCATION 128 - ZONE TYPE 10 ALARM EVENT CODE (1 segment, numerical data)
Location 128 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen
from the list on page 53. The zone ID will be that zone that is in alarm. If 4+2 format is being used, the number
programmed in this location will be sent as the tens digit. When using 4+2, the digit in location 128 should be from 1-
15. The zone ID for 4+2 formats will be the ones digit of the zone that is in alarm.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE NX-1308E - Caddx 8 Zone LED Keypad and is the answer not in the manual?

GE NX-1308E - Caddx 8 Zone LED Keypad Specifications

Power IconPower
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320E power supply12 VDC Regulated 2 AMPS
LED keypad current draw130 mA max.
LED keypad zones normal w/o sounder55 mA
NX-148E LCD keypad current draw110 mA max.
NX-148E LCD keypad w/o sounder75 mA
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
Loop Specifications IconLoop Specifications
standard loop resistance300 Ohms Maximum
2-wire smokes resistance30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Weight and Dimensions IconWeight and Dimensions
LED keypad width6.4"
LED keypad height4.0"
LED keypad depth1.1"
NX-148E LCD keypad width6.4"
NX-148E LCD keypad height5.3"
NX-148E LCD keypad depth1.0"
metal enclosure width11.25"
metal enclosure height11.25"
metal enclosure depth3.50"
shipping weight9 lbs.

Related product manuals