2.3.6.2 View / Edit settings (if all settings are enabled)
CB CONTROL
Password protected window for “CB CONTROL” settings:
TCS Alarm, TCS Timer, CB Open S’vision (Enabled/Disabled), CB Open
Time, CB Open Alarm (Enabled/Disabled), CB Open Oper, CB Control
By, Close Plus Time, Open Pulse Time and Emergency Rest (Yes/No).
TCS Alarm
Yes
Editable setting
By using the (+ /5) or (- /6) key, TCS Alarm can be set as Yes / No.
TCS Timer
5.00S
Editable setting
By using the (+ /5) or (- /6) key, TCS Timer can be set. The setting
range is from 0.1s to 10s in steps of 10ms.
CB Open S’vision
Enabled
Editable setting
By using the (+ /5) or (- /6) key, CB Open Supervision can be
Enabled or Disabled.
By using the (+ /5) or (- /6) key, CB Open Time can be set. The
setting range is from 50ms to 1s in steps of 10ms
CB Open Alarm
Enabled
Editable setting
By using the (+ /5) or (- /6) key, CB Open Alarm can be Enabled or
Disabled.
CB Open Oper
2000
Editable setting
By using the (+ /5) or (- /6) key, CB Open operations can be set. The
setting range is from 1 to 30000 in steps of 1.
CB Control by
Local + Remote
By using the (+ /5) or (- /6) key, CB Control By can be set as
Disabled/Local/Remote /Local + Remote.