5 Configuration
P50 Agile P253
5-28
P253/EN M/C
Measure’t setup
ABC
Editable setting
By using the (+ /5) or (- /6) key, Measurement Setup can be set as
ABC / RYB.
Setting Values
Secondary
Editable setting
By using the (+ /5) or (- /6) key, Setting Values can be set as Primary
/ Secondary.
2.3.9 Transformer Ratios Menu
2.3.9.1 View / Edit Settings
TRANS. RATIOS
Password protected window for “TRANS. RATIOS settings:
Phase CT Primary, Phase CT Secondary, E/F CT Primary and E/F CT
Secondary.
Phase CT Primary
100 A
Editable setting
By using the (+ /5) or (- /6) key, Phase CT Primary can be set. The
setting range is from 1A to 30000A in steps of 1A.
Phase CT Sec’y
1 A
Editable setting
By using the (+ /5) or (- /6) key, Phase CT Secondary can be set as
1A / 5A.
E/F CT Primary
100 A
Editable setting
By using the (+ /5) or (- /6) key, E/F CT Primary can be set. The
setting range is from 1A to 30000A in steps of 1A.
E/F CT Secondary
1 A
Editable setting
By using the (+ /5) or (- /6) key, E/F CT Secondary can be set as 1A /
5A.
2.3.10 Record Control Menu
2.3.10.1 View / Edit Settings
RECORD CONTROL
Password protected window for
“RECORD CONTROL’’
settings:
Clear Events (Yes/No), Clear Faults (Yes/No)
, Clear Dist Recs
(Yes/No), Clear Maint (Yes/No), Thermal Reset (Yes/No), Reset Nb Em
Rst (Yes/No), Reset Nb of St (Yes/No), Reset Motor RunT (Yes/No) and
Reset CB Data (Yes/No).