EasyManua.ls Logo

GE RAK148F2 - Troubleshooting Tips

GE RAK148F2
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
TROUBLESHOOTING TIPS
Problem Solution
No Display Check for 24 VAC; display is blank
when 24 VAC is not present
System fan does not
come on properly
Verify that wiring is correct.
All thermostat but-
tons are inoperative
Verify that 24 VAC is present; unit
will not operate when 24 VAC is not
present.
Thermostat turns on
and off too fre-
quently
Adjust temperature differential
VHH&RQ¿JXUDWLRQ0RGH6HWWLQJ
Temperature Differential, Stage 1 and
Stage 2 section).
Fan runs continu-
ously
Check Fan Auto/On switch. If set to
ON position, fan will run.
Room temperature
is not correct
Verify that wall hole is plugged with
SXWW\RULQVXODWLRQWRSUHYHQWDLUÀRZ
from the wall cavity. Adjust Tempera-
WXUH2IIVHWVHH&RQ¿JXUDWLRQ0RGH
- Room temperature offset section).
Compressor doesn’t
run or turn off im-
mediately when
changing function
or setting
There is a 3 minute time delay and
a 3 minute minimum run time for the
compressor when it turns on/off.
Fan doesn’t run or
turn off immedi-
ately when changing
function or setting
This is normal. On some models, the
fan may have a minimum run time/off
time delay.
Problem not listed
above
Press the Reset button once to reset
the thermostat and restore all factory
settings.

Related product manuals