Installation
Filling with SF
6
gas
GE Information07- 2016 L32- 007EN/07
1/8
Presentation
Warning
DUE TO THE RISK OF PROBLEMS DURING TRANSPORT,
BEFORE ANY INITIAL FILLING & COMMISSIONING OPERATIONS,
AFTER MAINTENANCE OR INTERVENTIONS,
THE CONDITION OF THE INSULATORS MUST BE VERIFIED VISUALLY.
ALL PERSONS PRESENT MUST TAKE SHELTER OR REMAIN AT
A MINIMUM SAFETY DISTANCE.
FOR CERAMIC DEVICES: APPROXIMATELY 50m
FOR COMPOSITES: THE HEIGHT OF THE DEVICE.
NOTE : It should be noted that the filler gas used must conform to IEC 60376.