EasyManua.ls Logo

GE SF6 - Replacing an Opening or Closing Electro- Magnet

GE SF6
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
Intervention on the FK3- 4 operating device
GE Information L51- 303EN/05
5/10
11- 2016
Replacing an opening or closing electro- magnet
Process
The table below gives the steps of replacing an opening or closing electro-
magnet :
Step Action Diagram
1 Disconnect the supply wires from
the coil (9).
10
10
11
9
9
2 Extract the blade spring (10) by
pressing outwards on the rivet with
a finger.
3 Removethecore(11).
4 Remove the faulty coil and replace
it by a new one carrying the same
reference.
5 Reinstall the core (11).
6 Reinstall the blade spring (10).
7 Connect supply wires to the new
coil (9).

Related product manuals