Installation
Filling with SF
6
gas
GE Information07- 2016 L32- 007EN/07
8/8
Moisture content of SF
6
gas in circuit- breaker
Principl e
This measurement is not required, the equipment being provided with molec-
ular sieves in sufficient quantity to give a dew point of 0C(32F) for an
ambient temperature of 20C(68F), this applies for a unit filled to its nominal
pressure for 2 or 3 months.