GE Multilin L60 Line Phase Comparison System 4-29
4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE
4
FOR 10 MIN! flash message will appear upon activation of the ten minute timeout or any other time a user attempts any
change to the defined tier during the ten minute timeout. The LOCAL ACCESS DENIED FlexLogic™ operand will be set to
“Off” after the expiration of the ten-minute timeout.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and
the L60 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
REMOTE ACCESS DENIED FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.