GE Multilin L60 Line Phase Comparison System 5-63
5 SETTINGS 5.2 PRODUCT SETUP
5
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state.
The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.