GE Multilin L60 Line Phase Comparison System 5-73
5 SETTINGS 5.3 SYSTEM SETUP
5
Figure 5–20: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2)
BREAKER 1
TROUBLE
(DEFAULT)
BREAKER 1
OPEN
(DEFAULT)
BREAKER 1
CLOSED
(DEFAULT)
Note: the BREAKER 1 TROUBLE LED
can be latched using FlexLogic™
AND
XOR
AND
AND
AND
AND
AND
AND
AND
OR
OR
AND
OR
AND
AND
AND
AND
AND
AND
AND
XOR
AND
AND
XOR
AND
AND
XOR
AND
AND
AND
AND
AND
AND
AND
AND
AND
AND
OR
AND
SETTING
= 3-Pole
= 1-Pole
BREAKER 1 MODE
SETTING
=Off
BREAKER 1 A/3P CLSDΦ
SETTING
=Off
BREAKER 1 CLSDΦB
SETTING
=Off
BREAKER 1 CLSDΦC
SETTING
=Off
BREAKER 1 EXT ALARM
SETTING
=Off
BREAKER 1 A/3P OPNDΦ
SETTING
=Off
BREAKER 1 OPENEDΦB
SETTING
=Off
BREAKER 1 OPENEDΦC
SETTING
=Off
BREAKER 1 OUT OF SV
SETTING
BREAKER 1 Toperate
0
SETTING
BREAKER 1 Toperate
0
SETTING
BREAKER 1 Toperate
0
from breaker
control logic
sheet 1,
827061AR
BKR ENABLED
FLEXLOGIC OPERAND
BREAKER 1 CLOSED
FLEXLOGIC OPERAND
BREAKER 1 OPEN
FLEXLOGIC OPERAND
BREAKER 1 DISCREP
FLEXLOGIC OPERAND
BREAKER 1 TROUBLE
FLEXLOGIC OPERAND
BREAKER 1 BAD STATUS
FLEXLOGIC OPERANDS
BREAKER 1 ΦA BAD ST
BREAKER 1 ΦA CLSD
BREAKER 1 ΦA OPEN
BREAKER 1 ΦA INTERM
FLEXLOGIC OPERANDS
BREAKER 1 Φ BAD STB
BREAKER 1 BΦ CLSD
BREAKER 1 BΦ OPEN
BREAKER 1 BΦ INTERM
FLEXLOGIC OPERANDS
BREAKER 1 CΦ BAD ST
BREAKER 1 CΦ CLSD
BREAKER 1 CΦ OPEN
BREAKER 1 CΦ INTERM
FLEXLOGIC OPERANDS
BREAKER 1 ANY P OPEN
BREAKER 1 1P OPEN
BREAKER 1 OOS
842025A1.CDR
SETTING
BREAKER 1 ALARM DELAY
0