EasyManua.ls Logo

GE UR series

GE UR series
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-120 L60 Line Phase Comparison System GE Multilin
5.5 GROUPED ELEMENTS 5 SETTINGS
5
The negative-sequence overcurrent advanced fault detector element responds to the increment of the magnitude of the
negative-sequence current over a specified threshold. Thresholds are provided for low-set control of keying and high-set
operation control of tripping.
The following settings are available.
NEG SEQ I_2 FD FUNCTION: This setting enables or disables the negative-sequence overcurrent fault detection.
Note that all fault detectors operate in parallel with the 87PC function. To effectively disable the overcurrent fault detec-
tors under the main 87PC menu, set their threshold very high.
NEG SEQ I_2 FDL PICKUP: This setting specifies the pickup of the low-set stage of the element used to control the
key operation. The nominal current of the phase CT bank of the relay is 1 pu.
NEG SEQ I_2 FDH PICKUP: This setting specifies the pickup of the high-set stage of the element used to control the
trip operation. The nominal current of the phase CT bank of the relay is 1 pu.
NEG SEQ I_2 BLK: The fault detector is hard-wired to the 87PC scheme. It can be disabled permanently using the
function setting or blocked temporarily with this setting. This setting selects a FlexLogic™ operand that blocks this fault
detector when asserted.
NEG SEQ I_2 FD TARGET: This setting controls targets of the negative-sequence overcurrent advanced fault detector
function. These targets operate independently from the 87PC targets.
NEG SEQ I_2 FD EVENTS: This setting controls event recording of the negative-sequence overcurrent advanced fault
detector function. These events are logged independently from the 87PC events.
Figure 5–50: NEGATIVE-SEQUENCE OVERCURRENT ADVANCED FAULT DETECTOR LOGIC
h) POSITIVE-SEQUENCE OVERCURRENT FAULT DETECTION
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö PHASE COMPARISON ELEMENTS ÖØ ADVANCED FAULT DETECTORS
ÖØ POSITIVE-SEQUENCE CURRENT
POSITIVE-SEQUENCE
CURRENT
POS SEQ I_1 FD
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POS SEQ I_1 FDL
PICKUP: 0.10 pu
Range: 0.20 to 5.00 pu in steps of 0.01
MESSAGE
POS SEQ I_1 FDH
PICKUP: 0.50 pu
Range: 0.50 to 15.00 pu in steps of 0.01
MESSAGE
POS SEQ I_1 BLK:
Off
Range: FlexLogic™ operand
MESSAGE
POS SEQ I_1 FD
TARGET: Self-reset
Range: Self-Reset, Latched, Disabled
MESSAGE
POS SEQ I_1 FD
EVENTS: Disabled
Range: Disabled, Enabled
Hardwired to the
87PC function
To square pulse
and transmit logic
SETTINGS
Enabled = 1
Disabled = 0
NEG SEQ I_2 FD FUNCTION
Off=0
NEG SEQ I_2 BLOCK
AND
FAST MEASUREMENTS
Negative-sequence
current I_2
F1 PHASE CT BANK
L1 PHASE CT BANK
Negative-sequence
current I_2
Σ
SETTINGS
NEG SEQ I_2 FDH PICKUP
RUN
NEG SEQ I_2 FDL PICKUP
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> FDL PICKUP
> FDH PICKUP
OR
OR
AND
AND
FLEXLOGIC OPERANDS
87PC I_2 FDL OP
87PC I_2 FDH OP
831030A1.CDR

Table of Contents

Other manuals for GE UR series

Related product manuals