GE Multilin L60 Line Phase Comparison System 5-239
5 SETTINGS 5.6 CONTROL ELEMENTS
5
5.6.11 AUTORECLOSE
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ AUTORECLOSE Ö AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR MODE:
1 & 3 Pole
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
MESSAGE
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
MESSAGE
AR BLOCK BKR1:
Off
Range: FlexLogic™ operand
MESSAGE
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR BKR MAN CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
AR BLK TIME UPON MAN
CLS: 10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 1P INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3P INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3P TD INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR MULTI-P FAULT:
Off
Range: FlexLogic™ operand
MESSAGE
BKR ONE POLE OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 3 POLE OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 4:
4.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR EXTEND DEAD T 1:
Off
Range: FlexLogic™ operand
MESSAGE
AR DEAD TIME 1
EXTENSION: 0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR RESET:
Off
Range: FlexLogic™ operand
MESSAGE
AR RESET TIME:
60.00 s
Range: 0 to 655.35 s in steps of 0.01