GE Multilin L60 Line Phase Comparison System E-7
APPENDIX E E.1 DEVICE PROFILE DOCUMENT
E
34
cont’d
2 32-bit Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
(see Note 2)
2
(write) 00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
3 Short floating point Analog Input Reporting
Deadband
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
(see Note 2)
50 1 Time and Date
(default – see Note 1)
1 (read)
2 (write)
00, 01 (start-stop)
06 (no range, or all)
07 (limited qty=1)
08 (limited quantity)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
(see Note 2)
52 2 Time Delay Fine 129
(response) 07 (limited quantity)
(quantity = 1)
60 0 Class 0, 1, 2, and 3 Data 1 (read)
20 (enable unsol)
21 (disable unsol)
22 (assign class)
06 (no range, or all)
1 Class 0 Data 1 (read)
22 (assign class)
06 (no range, or all)
2 Class 1 Data 1 (read)
20 (enable unsol)
21 (disable unsol)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
3Class 2 Data
4Class 3 Data
70 0 File event - any variation 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
22 (assign class) 06 (no range, or all)
2 File authentication 29 (authenticate) 5b (free format) 129 (response) 5b (free format)
3 File command 25 (open)
27 (delete)
5b (free format)
4 File command status 26 (close)
30 (abort)
5b (free format) 129 (response)
130 (unsol. resp.)
5b (free format)
5 File transfer 1 (read)
2 (write)
5b (free format) 129 (response)
130 (unsol. resp.)
5b (free format)
6 File transfer status 129 (response)
130 (unsol. resp.)
5b (free format)
7 File descriptor 28 (get file info.) 5b (free format) 129 (response)
130 (unsol. resp.)
5b (free format)
80 1 Internal Indications 1 (read) 00, 01 (start-stop)
(index =7)
129 (response) 00, 01 (start-stop)
2 (write)
(see Note 3)
00 (start-stop)
(index =7)
--- No Object (function code only)
see Note 3
13 (cold restart)
--- No Object (function code only) 14 (warm restart)
--- No Object (function code only) 23 (delay meas.)
Table E–2: IMPLEMENTATION TABLE (Sheet 4 of 4)
OBJECT REQUEST RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
FUNCTION
CODES (DEC)
QUALIFIER
CODES (HEX)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the L60 is not restarted, but the DNP process is restarted.