Relay not Responding 
This fault is raised when the ECU double knock relay does not switch when required. The relay is 
mapped as an output that is activated by a triggered input. 
Indications 
•  Fault buzzer sounds. 
•  Display scrolls between two events, one showing the addressable relay device that has not 
switched, the other showing the event that has triggered it (usually a fire event). For example: 
FIRE    Zone 001  Dev 001   Event 001 
Second Floor,   Laundry Room 
 
RELAY FAULT   Zone 001  Dev 086   Event 002 
 
•  Events are printed (if printer configured). 
•  Zone in which the relay fault occurred is indicated by the appropriate red Zone LED. 
Possible Causes 
•  ECU double knock relay is in an isolated state. 
•  ECU double knock relay is faulty. 
Corrective Actions 
1.  Press the ACCEPT button to accept the fault. 
2.  If the yellow Isolated LED is on, check whether the relay is isolated. If the relay is isolated then 
investigate the reasons for this. De-isolate the relay if it is safe to do so. 
3.  If no other reason can be found for the fault, replace the faulty ECU main board. 
4.  Reset the panel. 
Device Type Fault 
When the system is commissioned the panel notes the device type at each address. If this type 
should subsequently change then the panel raises a device type fault. 
Indications 
•  Yellow Fault LED is lit. 
•  Fault buzzer sounds. 
•  Event is shown on the display, for example: 
TYPE FAULT  Zone 001  Dev 001  Event 001 
Second Floor, Laundry Room 
•  Event is printed (if printer configured).