5.10 Function test of the trigger unit INT69 G
Beforecommissioning,aftertroubleshootingormakingchangestothecontrolpowercircuit,check
thefunctionalityofthetriggerunit.Performthischeckusingacontinuitytesterorgauge.
5| Electrical connection
Gauge state Relay position
1.
Deactivatedstate 11-12
2.
INT69Gswitch-on 11-14
3.
RemovePTCconnector 11-12
4.
InsertPTCconnector 11-12
5.
Resetaftermainson 11-14
5.11 Start unloader
To avoid current peaks during the starting phase we recommend using the GEA Bock-ESS soft
startingdevice(ElectronicSoftStart).Referto"Accessories"forfurtherinformation.