22
D
GB
F
E
09618-05.2012-DGbFEI
8| Technical data
Type No. of
cylin-
ders
Displace-
ment
50/60Hz
(1450 / 1740
rpm
)
Electrical data
Weight
Connections Oil
charge
Sound pres-
sure level
Voltage Max.
Operating
current
∆ / Y
Max.
power
consump-
tion
Starting
current
(rotor
locked)
∆ / Y
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr. dB(A)
HG34P/215-4
4
18,8/22,6 14,4/8,3 5,0 67 / 40 92
16 (
5
/
8
)
22 (
7
/
8
)
1,3
62 / 59 / 58
HG34P/215-4 S
18,8/22,6 18,1/10,5 6,1 96 / 57 95 62 / 59 / 58
HG34P/255-4
22,1/26,6
17,3/10,0 6,1 67 / 40 91
28 (1
1
/
8
)
64/62/60,5
HG34P/255-4 S
22,1/26,6
21,8/12,6 7,5 96 / 57 94
64/62/60,5
HG34P/315-4
27,3/32,8
21,1/12,2 7,3 96 / 57 94
22 (
7
/
8
)
66 / 64 / 63
HG34P/315-4 S
27,3/32,8
26,5/16,3 8,9 134 / 77 97 66 / 64 / 63
HG34P/380-4
33,1/39,7
26,1/15,1 9,1 96 / 57 93
67/64,5/64
HG34P/380-4 S
33,1/39,7
32,4/18,7 11,1 134 / 77 96
67/64,5/64
1
2
3
2
4
220-240 V ∆ / 380-420 V Y - 3 - 50 Hz
265-290 V ∆ / 440-480 V Y - 3 - 60 Hz
L / M / H
5
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
designoffuses,supplylinesandsafetydevices.Fuse:Consumption
category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L=lowtemperature(-35/40°C),M=normalcooling(-10/45°C),
H = air conditioning (5 / 50°C)
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressoroperationat50Hz(1450rpm),refrigerantR404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4