7.6 Decommissioning
Close the shut-off valves on the compressor. CO
2
does not need to be recycled and can therefore
be blown off into the environment. It is essential to ensure good ventilation or conduct the CO
2
into
the outdoors to avoid danger of suffocation. When releasing CO2, avoid a fast drop in pressure to
prevent oil from exiting with it. If the compressor is unpressurized, remove the piping on the pressure-
and suction-side (e.g. dismantling of the shut-off valve, etc.) and remove the compressor using an
appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.
When decommissioning the compressor (eg. for service or replacement of the compressor) larger
amounts of CO
2
intheoilcanbesetfree.Ifthedecompressionofthecompressorisnotsufcient
enough, closed shut-off valves may lead to intolerable excessive pressure. For this reason the suction
side (LP) and the high pressure side (HP) of the compressor have to be secured by decompression
valves.