5| Electrical connection
5 Electrical connection
DANGER! Highvoltage!Riskofelectricshock!Onlycarryoutworkwhenthe
electrical system is disconnected from the power supply!
INFO!
Connectthecompressormotorinaccordancewiththecircuitdiagram
(seeinsideofterminalbox).
Use suitable cable entry point of the correct protection type
(see name plate) for routing cables into the terminal box.
Insert the strain reliefs and prevent chafe marks on the cables.
Comparethevoltageandfrequencyvalueswiththedataforthemains
powersupply.
Only connect the motor if these values are the same.
5.1 Information for contactor and motor contactor selection
Allprotectionequipment,switchingandmonitoringdevicesmustcomplywiththelocalsafetyregula-
tionsandestablishedspecications(e.g.VDE)andregulationsaswellasthemanufacturer’sspecica-
tions.Motorprotectionswitchisrequired!Motorcontactors,feedlines,fusesandmotorprotection
switchesmustberatedaccordingtothemaximumoperatingcurrent(seenameplate).
Usethefollowingoverloadprotectiondevice:
Acurrent-dependenttime-delayedoverloadprotectiondeviceformonitoringofallthreephases,not
sethigherthantheratedcurrentofthemachine,whichmustrespondat1.2timesthesetcurrent
within2hoursandmustnothaverespondedat1.05timesthesetcurrentwithin2hours,oranother
comparabledevice.