6| Commissioning
6.1 Preparations for start-up
INFO! In order to protect the compressor against inadmissible operating
conditions,high-pressureandlow-pressurepressostats controls are
mandatory on the installation side.
Thecompressorhasundergonetrialsinthefactoryandallfunctionshavebeentested.Thereare
thereforenospecialrunning-ininstructions.
Checkthecompressorfortransportdamage!
6.4 Evacuation
ATTENTION! Do not start the compressor if it is under vacuum. Do not apply
any voltage - even for test purposes (must only be operated with
refrigerant).
Undervacuum, the spark-over and creepage current distancesof the
terminalboardconnectionboltsshorten;thiscanresultinwindingand
terminalboarddamage.
Firstevacuatethesystemandthenincludethe compressor in the evacuation process.
Relievethecompressorpressure.
Openthesuctionandpressurelineshut-offvalves.
Evacuatethesuctionanddischargepressuresidesusingthevacuumpump.
Attheendoftheevacuationprocess,thevacuumshouldbe<1.5mbarwhenthepumpisswitchedoff.
Repeatthisprocessasoftenasisrequired.
6.2 Pressure strength test
DANGER! Bursting! The compressor must only be pressurised using nitrogen
(N
2
). Never pressurise with oxygen or other gases!
The maximum permissible overpressure of the compressor must not
be exceeded at any time during the testing process (see name plate
data)! Do not mix any refrigerant with the nitrogen as this could
cause the ignition limit to shift into the critical range.
Thecompressorhasbeenfactory-testedforpressureresistance.Thefollowingmustbeobservedif
theentireplantissubjectedtoanadditionalpressurestrengthtest:
TesttherefrigerationcircuitaccordingtoEN378-2oracorrespondingsafetystandard.
6.3 Leaktest
DANGER! Bursting!
Do not mix any refrigerant with the nitrogen (N
2
) as this could cause
the ignition limit to shift into the critical range.
CarryouttheleaktestoftherefrigeratingsysteminaccordancewithEN378-2oracorresponding
safetystandardwithout including the compressor.