GH20SB – User Manual PAGE 24
Setting
Regulacja obrotów
pompy kolektorów
(Collector pump
rotation speed
adjustment)
RegFaz
Main pump (collector pump) adjustment. If the
collector pump adjustment is selected in the Controller
settings, the Controller will adjust the collector pump
rotation speed. If the collector pump speed adjustment
option is disabled, the Controller will only control the
pump in the on/off operation mode.
In schemes 6, 10, 12, 14, 15 and 16 the collector pump
rotation speed adjustment is never active.
Tryb pracy pompy
cyrkulacyjnej
(Circulation pump
operation mode)
When it is set to “Ciągły” (Continuous), the
circulation pump is activated in the hours set in the
“Program czasowy” (Time Programme) menu. If it is
set to “Przerywana” (Intermittent), the circulation
pump will additionally operate in the hours set in the
“Program czasowy” (Time Programme) menu,
however, it will operate on a cyclical basis, activating
for 10 minutes, then after 10 minutes deactivating for
another 10 minutes after it will again activate for 10
minutes.
Interm. /
Contin.
Moc kolekt. wyłącz.
kotła, grzałki,
pompy ciepła
(Collector power for
deactivated boiler,
heater, heat pump)
Setting applied in schemes 3, 4, 5 and 14. The
Controller calculates the collector power and
deactivates the boiler or the heater if the calculated
power exceeds the power defined in the control
setting. When the collector power value is lower than
the value defined in the settings, the boiler, heater and
pump outputs are controlled in accordance with their
control algorithm.
Ochrona przed
przegrzaniem
kolektorów
(Collector
overheating
prevention)
Setting defines enabling or disabling the boiler
overheating prevention function.
No / Yes
Max. temp. T2
wyłącz. ochrony
przegrz. kolektorów
(Max. T2
temperature for
deactivating
collector
overheating
prevention)
Setting defines the maximum temperature within the
tank when the collector overheating function is
enabled. This setting has priority over the
T2
max
.setting.
60…85ºC
Ochrona przed
zamrożeniem
kolektorów
(Collector freezing
prevention)
Setting enables/disables the collector freezing
prevention function.
No / Yes
Wybór priorytetu
grzania (Heating
priority selection)
Setting associated with schemes 9, 10, 11, 12 and 16.
Defines the priority of the tank / pool heating.
A / B
Ochrona przed
bakteriami
Legionella
(Protection from
Legionella)
Setting associated with schemes 3, 4, and 14. Defines
whether the anti-legionella function is enabled or
disabled.
No / Yes