TYPE 3
20MA  = Sensor 0...20 mA
4-20M  = Sensor 4...20 mA
10V  = Sensor 0...10 V
2-10V  = Sensor 2...10 V
5V  = Sensor 0...5 V
1-5V  = Sensor 1...5 V
2.4VHI  = Sensor 0…2.4V high impedance
1.2VHI  = Sensor 0…1.2V high impedance
1VHI = Sensor 0…1V high impedance
C.20MA  = Sensor 0...20 mA with custom calibration
C.4-20  = Sensor 4...20 mA with custom calibration
C.10V  = Sensor 0...10 V with custom calibration
C.2-10  = Sensor 2...10 V with custom calibration
C.5V  = Sensor 0...5 V with custom calibration
C.1-5V  = Sensor 1...5 V with custom calibration
C2.4VH  = Sensor 0...2.4 V high impedance with custom calibration
C1.2VH  = Sensor 0...1.2  V high impedance with custom calibration
4.9.4.  SBR.E - Enabling SBR error 
Acronym Scrolling message Submenu Attributes
SBR.E INPUT.1 (or INPUT.2) SBR ENABLE INPUT R W
Enables open thermocouple probe error detection, also permitting infrared sensor management with maximum 4Kohm 
output impedance. 
This parameter only appears when a thermocouple type input is selected. 
When OFF, the parameter will be forced to ON (see options) at each Power On 
Unit of measurement: -
Options:  OFF = Disable SBR alarm 
  On = Enable SBR alarm 
  On.t = Enable SBR alarm with timing