80209C_MHW_850-1650-1850_02-2020_ENG_pag. 89
TYPE 3
20MA = Sensor 0...20 mA
4-20M = Sensor 4...20 mA
10V = Sensor 0...10 V
2-10V = Sensor 2...10 V
5V = Sensor 0...5 V
1-5V = Sensor 1...5 V
2.4VHI = Sensor 0…2.4V high impedance
1.2VHI = Sensor 0…1.2V high impedance
1VHI = Sensor 0…1V high impedance
C.20MA = Sensor 0...20 mA with custom calibration
C.4-20 = Sensor 4...20 mA with custom calibration
C.10V = Sensor 0...10 V with custom calibration
C.2-10 = Sensor 2...10 V with custom calibration
C.5V = Sensor 0...5 V with custom calibration
C.1-5V = Sensor 1...5 V with custom calibration
C2.4VH = Sensor 0...2.4 V high impedance with custom calibration
C1.2VH = Sensor 0...1.2 V high impedance with custom calibration
4.9.4. SBR.E - Enabling SBR error
Acronym Scrolling message Submenu Attributes
SBR.E INPUT.1 (or INPUT.2) SBR ENABLE INPUT R W
Enables open thermocouple probe error detection, also permitting infrared sensor management with maximum 4Kohm
output impedance.
This parameter only appears when a thermocouple type input is selected.
When OFF, the parameter will be forced to ON (see options) at each Power On
Unit of measurement: -
Options: OFF = Disable SBR alarm
On = Enable SBR alarm
On.t = Enable SBR alarm with timing