12 ADV50 QS, SW-PW V1.11 / CTL V2.11
Italiano English
Italiano English
Pr. Explanation Settings
Factory
Setting
NOTE
01.24
Delay Time at 40Hz
for Simple Position
0.00 to 600.00 sec 0.00
01.25
Delay Time at 50Hz
for Simple Position
0.00 to 600.00 sec 0.00
01.26
Maximum Voltage
Frequency (Fbase)
(Motor 1)
0.10 to 600.0 Hz 60.00
115V/230V series: 0.1V to 255.0V 220.0
01.27
Maximum Output
Voltage (Vmax)
(Motor 1)
460V series: 0.1V to 510.0V 440.0
01.28
Mid-Point Frequency
(Fmid) (Motor 1)
0.10 to 600.0 Hz 1.50
115V/230V series: 0.1V to 255.0V 10.0
01.29
Mid-Point Voltage
(Vmid) (Motor 1)
460V series: 0.1V to 510.0V 20.0
01.30
Minimum Output
Frequency (Fmin)
(Motor 1)
0.10 to 600.0 Hz 1.50
115V/230V series: 0.1V to 255.0V 220.0
01.31
Minimum Output
Voltage (Vmin) (Motor
1)
460V series: 0.1V to 510.0V 440.0
01.32
Maximum Voltage
Frequency (Fbase)
(Motor 2)
0.10 to 600.0 Hz 60.00
115V/230V series: 0.1V to 255.0V 220.0
01.33
Maximum Output
Voltage (Vmax)
(Motor 2)
460V series: 0.1V to 510.0V 440.0
01.34
Mid-Point Frequency
(Fmid) (Motor 2)
0.10 to 600.0 Hz 1.50
115V/230V series: 0.1V to 255.0V 10.0
01.35
Mid-Point Voltage
(Vmid) (Motor 2)
460V series: 0.1V to 510.0V 20.0
01.36
Minimum Output
Frequency (Fmin)
(Motor 2)
0.10 to 600.0 Hz 1.50
115V/230V series: 0.1V to 255.0V 10.0
01.37
Minimum Output
Voltage (Vmin) (Motor
2)
460V series: 0.1V to 510.0V 20.0
01.38
Maximum Voltage
Frequency (Fbase)
(Motor 3)
0.10 to 600.0 Hz 60.00
115V/230V series: 0.1V to 255.0V 220.0
01.39
Maximum Output
Voltage (Vmax)
(Motor 3)
460V series: 0.1V to 510.0V 440.0

Related product manuals