ENG GEMAŞ STEAM GENERATOR AND CONTROL PANEL INSTRUCTIONS MANUAL V2.1
Description About Electricty
ELECTRICAL AND MECHANICAL MEASURES HAVE BEEN TAKEN IN THE STEAM
GENERATOR TO PROTECT THE SAFETY AND GOODS SAFETY. WARNINGS ON THE
LEAKAGE CURRENT RELAY AND EARTHING MUST BE CONSIDERED TO
CONSIDER THE FUNCTION OF ELECTRICAL MEASURES.
Leakage relay: Use a 4x25 A / 30 mA CE certified residual current relay and make sure it is
working. Make sure that the relay you will use is near the device and only controls the
generator. Do not share with other devices. Strictly test the Leakage Current Relay every year.
The manufacturer / seller company cannot be held responsible for any problems that
may arise from the failure of the Leakage Current Relay or its subsequent failure or
cancellation.
Supply Cable: Device supply cable must be at least 5x4mm. Connect this cable to the fuse
you will install right next to the device. Consider the distance between the main panel and the
generator fuse, use a cable with a minimum cross section of 4mm2.
Grounding: Make sure the grounding in your facility is well done. Always connect the
grounding line of the installation to the terminal on the device. If necessary, test the grounding
line. You must also see the voltage value you see between phase and neutral between phase /
ground. The neutral and ground voltage value must be at most 2 VAC.
L1-N: 220V L1-PE: 220V N-PE: Maximum 2V
The manufacturer / seller company cannot be held responsible for any
problems that may arise from not connecting the ground wire or poor
grounding.