Setting Travel Limits
UP LIMIT SET
Figure 7
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
DOWN LIMIT SET
Figure 8
NOTE: The recommended setpoint for the DOWN Travel Limit is normally at
approximately 2 inches off the floor. This final distance will be covered by the Limit
Overrun Function to establish a more accurate seal.
CAL
RUN
SCROLL
SET
CLEAR
OPEN
SCROLL
CAL
RUN
CLOSE
CLOSE
Resetting Travel Limits
CAL
RUN
CROL
OPEN
SET
CLEAR
CAL
RUN
SET
CLEAR
UP and/or DOWN
1) If operator is in RUN mode, press CAL/RUN to enter calibration mode.
2) Press SCROLL until display reads “UP LIMIT>CLR or
“DOWN LIMIT>CLR Figure 7
.
3) Jog the door using the OPEN or CLOSE key until you reach the
desired height.
4) Press SET/CLEAR key to switch display to “UP LIMIT>SET “ or
“DOWN LIMIT>SET .“ Figure 8.
5) Press a SCROLL key to shift to a new function and lock in the
limit setting.
limit setting.
SCROLL
6) Press a SCROLL key to shift to a new function and lock in the
6) Press CAL/RUN to return to run mode.
UP and/or DOWN
1) If operator is in RUN mode, press CAL/RUN to enter calibration mode.
2) Press SCROLL until display reads “UP LIMIT>SET or
“DOWN LIMIT>SET.” Figure 8.
3) Press SET/CLEAR to switch display to ”UP LIMIT>CLR” or
”DOWN LIMIT>CLR”
4) Jog the door using the OPEN or CLOSE key until you reach the
5) Press SET/CLEAR to switch display to ”UP LIMIT>SET” or
”DOWN LIMIT>SET”
7) Press CAL/RUN to return to run