Battery Model: select the battery model to be connected.
Battery Over-voltage/Under-voltage Protection: fill in the appropriate data to protect the
battery and extend its life.
Over-discharge SOC: when the battery is discharged to the over-discharge SOC,
the battery will not discharge actively.(Due to the internal current conduction, there is a
small self-consumption power, if not charged for a long time, the SOC will slowly continue
to decline.)
Force-charge SOC: due to the battery power consumption, when the over-discharge SOC
drops to the force-charge SOC, the inverter will directly charge the battery according to
the maximum battery charging current until the battery SOC reaches the over-discharge
SOC.(The charging power is not limited to sources, which may be from PV or from the grid.
If”Charging form grid” is set to “Not Allow”,the charging logic may not be implemented.)
It is not recommended to set the over-discharge&force-charge SOC to the same value,
which may cause frequent charging and discharging.
Battery Setting
Meter type: please select a correct meter type. The wrong option will cause the meter
RS485 communication Failed. If the battery and meter are not connected, you can select
the”NO Meter” to shield the alarm of meter communication fault.
Meter Installation Location: Meter in Grid/Meter in Load/Grid +PV inverter.
Meter Setting
6. Operation
User Manual
42
Battery Setting
Battery Model
Dyness LV
Battery Overvoltage Protection
Setting
60.0V
Battery Undervoltage Protection
Setting
42.0V
Forcecharge Limited Power
Setting
5000W
Forcecharge Power Source Setting
Only Use...
Overdischarge SOC
20%
Forcecharge SOC
10%
<
>
>
>
>
>
>
>
Cancel
Meter Setting
Save
Meter Type
Eastron Standard 1P Meter
Eastron Standard 3P Meter
NO Meter