EasyManuals Logo

Ginlong Solis User Manual

Ginlong Solis
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
8. Troubleshooting8. Troubleshooting
.67..66.
Alarms
Cause Solution
Inverter detects grid
Frequency as too high
OV-G-F: Over
Grid Frequency
Test – DC switch OFF
Check frequency at the inverter test points
If Frequency measures high, adjust upper
limit with permission from utility
Check LCD reading, may be a bad
measurement circuit
Test – DC Switch ON
Check grid standard
Replace inverter
NO-GRID
Inverter does not
detect the grid
Test – DC switch OFF
Check AC at the inverter test points
L-L, L-GND
Check LCD reading, may be a bad
measurement circuit
Test – DC Switch ON
Check grid standard
Replace inverter
OV-DC: DC
voltage is too
high
Inverter detects High DCV
Test – DC switch OFF
Check DC at the inverter test points
If DCV is high, too many panels in the string
Test – DC Switch ON
Check LCD reading, may be a bad
measurement circuit
Replace inverter
OV-BUS: DC
BUS voltage is
too high
Inverter detects High
DCV on internal bus
Test
Measure DC and AC voltages
Compare with LCD
Replace Inverter
Internal damage
Wire came loose during shipping
UN-BUS: DC
BUS voltage is
too low
Inverter detects low DCV
on internal bus
Test
Measure DC and AC voltages
Compare with LCD
Replace Inverter
Internal damage
Wire came loose during shipping
Alarms
Cause Solution
Input voltage low/missing
Polarity reversed
Main board damaged
No Information
(Blank Screen)
Test – DC switch OFF
Check PV connections
Check polarity
Check voltage >860V
Test – DC Switch ON
Check voltage >860V
If DC voltage is “0” replace inverter
Initializing
(Inverter stuck
in this mode)
Inverter is waiting for
driving signal
Test – DC switch OFF
Check PV connections
Check polarity
Check voltage >860V
Test – DC Switch ON
Check voltage >860V
A cable may have been damaged or loosened
in shipping replace inverter
OV-G-V: Over
Grid Voltage
Inverter detects grid
voltage as too high
Test – DC switch OFF
Check AC at the inverter
If AC measures high, adjust upper limit with
permission from utility
Test – DC Switch ON, full power
Check AC at inverter test points
Compare with LCD
If AC measures high, cables between inverter
and interconnect are too small
Check ampacity and voltage drop calculations
UN-G-V: Under
Grid Voltage
Inverter detects grid
voltage as too low
Test – DC switch OFF
Check AC at the inverter test points
If AC measures low, adjust lower limit with
permission from utility
Check LCD voltage reading, may be a bad
measurement circuit
Test – DC Switch ON
Check grid standard
Replace inverter
Screen OFF
with DC applied
Inverter internally
damaged
Do not turn off the DC switches as it may
damage the inverter.
Please wait for sunset and confirm the string
current is less than 0.5A with a clip-on ammeter
and then turn off the DC switch. String current
above 0.5A is under load.
Note: Damage due to wrong connections or fire
caused by removing string wires under load is
not covered in the device warranty.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ginlong Solis and is the answer not in the manual?

Ginlong Solis Specifications

General IconGeneral
Number of MPP Trackers2
Cooling MethodNatural Convection
Protection LevelIP65
ModelSolis
TypeGrid-Tied Inverter
AC Output Voltage230V
AC Output Frequency50 Hz / 60 Hz
Operating Temperature Range-25°C to 60°C
Warranty5 years

Related product manuals