GPH15 BLOWER PERFORMANCE DATA
NOTES:
• Data shown is dry coil. Wet coil pressure drop is approximately 0.1" H
2
0, for two-row indoor coil;
0.2" H
2
0, for three-row indoor coil; and 0.3" H
2
0, for four-row indoor coil.
Data shown does not include filter pressure drop, approximately 0.08" H
2
0.
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON.
• Reduce airflow by 2% for 208-volt operation.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 882 808 727 649 545 --- --- ---
WATTS 82 86 92 102 108 --- --- ---
CFM 933 873 810 733 637 584 --- ---
WATTS 93 103 109 120 126 135 --- ---
CFM 1058 1012 945 896 816 723 672 ---
WATTS 124 136 142 153 168 172 179 ---
CFM 893 824 752 665 575 --- --- ---
WATTS 87 95 101 111 115 --- --- ---
CFM 1132 1070 1011 959 889 827 733 669
WATTS 153 162 168 179 184 195 206 208
CFM 1287 1236 1165 1123 1066 1012 958 857
WATTS 211 217 228 239 244 255 265 272
CFM 852 764 711 592 545 --- --- ---
WATTS 80 82 86 95 99 --- --- ---
CFM 1232 1190 1131 1082 1023 966 889 819
WATTS 202 214 221 229 235 246 258 264
CFM 1267 1213 1162 1120 1058 1009 932 841
WATTS 218 226 236 245 247 260 272 275
GPH1530M41*
T1 (G) 230
T2 / T3
(W2)
230
T4 / T5 (Y) 230
GPH1524M41*
T1 (G)
T2 / T3
(W2)
T4 / T5 (Y)
230
230
230
E.S.P (In. of H
2
O)
230
Model Speed Volts
GPH1536M41*
T1 (G)
T2 / T3
(W2)
T4 / T5 (Y)
230
230