Questions and Answers

  • C
    Chad RodriguezSep 10, 2025
    What to do if my Goodwe HT 73-136kW Inverter displays 'Relay Fail'?
    • C
      Crystal KaufmanSep 10, 2025
      If your Goodwe Inverter is showing a 'Relay Fail' error, it could be due to several reasons: the relay itself is abnormal or short-circuited, the control circuit is malfunctioning, or there's an issue with the AC cable connection, such as a loose connection or short circuit. To resolve this, disconnect the AC output switch and DC input switch, wait 5 minutes, and then reconnect them. If the problem continues, contact your dealer or after-sales service for further assistance.
  • A
    andrea98Aug 22, 2025
    Why does my Goodwe HT 73-136kW Inverter show a 'Vac Fail' error?
    • N
      Nathan WilliamsAug 23, 2025
      If your Goodwe Inverter displays 'Vac Fail', it means the utility grid voltage is outside the acceptable range. Ensure the grid voltage is within the allowed range. Also, check that the phase sequence of the AC cables is correct, and the neutral wire and PE cable are properly and securely connected.
  • U
    umurrayAug 25, 2025
    What to do if my Goodwe Inverter displays 'Isolation Fail'?
    • T
      Timothy HendricksAug 25, 2025
      If your Goodwe Inverter shows 'Isolation Fail', it may be caused by a short circuit to the ground in the PV system or moisture affecting the circuit's insulation. Check the PV input cables for any breaks. Ensure the module frames and metal bracket are securely grounded, and verify the AC side is properly grounded. In Australia and New Zealand, inverters with WiFi will send an email about the fault automatically. If there is no WiFi, the inverter's buzzer will sound for 1 minute, repeating every 30 minutes if the problem continues.
  • R
    Raymond WilliamsAug 26, 2025
    How to fix 'Over Temperature' error on Goodwe HT 73-136kW Inverter?
    • C
      Christian MartinAug 27, 2025
      If your Goodwe Inverter displays 'Over Temperature', it could be due to poor ventilation, high ambient temperature, or the inverter working improperly. Check the installation environment to ensure it meets ventilation requirements for heat dissipation. Make sure the fans are working correctly and are not blocked. Also, verify that the operating ambient temperature is not too high.
  • S
    sabrinalittleAug 27, 2025
    What does 'Fac Fail' mean on a Goodwe Inverter?
    • B
      bandersonAug 27, 2025
      If your Goodwe Inverter displays 'Fac Fail', it indicates that the utility grid frequency is outside of the allowed range. Check whether other electrical devices under the same grid connection point are working normally, and whether the main supply is normal. Ensure the grid frequency is within the allowed range. Make sure that the phase sequence of the AC cables are connected correctly, and the neutral wire and PE cable are connected properly and firmly. If the fault occurs occasionally, it may be due to an instantaneous utility grid frequency change and may not require action.
  • R
    Richard FloresAug 29, 2025
    How to troubleshoot 'ARC Fault' on Goodwe HT 73-136kW?
    • H
      hudsoncarolineAug 29, 2025
      If your Goodwe Inverter shows 'ARC Fault', it indicates that the PV string cables are arcing or have poor contact. Check the PV terminals and cables to ensure they are properly connected. Clear the error messages. If the fault occurs frequently, contact after-sales service.
  • K
    kathleenhansonSep 18, 2025
    How to fix 'SPI Comm Fail' on my Goodwe Inverter?
    • M
      Mr. Joseph GomezSep 18, 2025
      If your Goodwe Inverter displays 'SPI Comm Fail', it could be due to the chip not being powered on or the chip program version being incorrect. To attempt a resolution, disconnect the AC output switch and DC input switch, then reconnect them after 5 minutes. If the problem persists, contact your dealer or after-sales service.
  • A
    Anthony ThomasSep 12, 2025
    What does 'Night BUS Fault' mean on my Goodwe Inverter?
    • T
      thomasrandySep 12, 2025
      If your Goodwe Inverter displays the 'Night BUS Fault' message, it means there is a problem with the utility grid power or the AC cable is disconnected, or the AC breaker is off. To attempt a fix, disconnect the AC output switch and DC input switch, wait 5 minutes, then reconnect them. If the issue persists, contact your dealer or after-sales service.
  • J
    Jose DonovanSep 8, 2025
    Why does my Goodwe HT 73-136kW Inverter show 'Fac Fail'?
    • L
      Lori Simmons MDSep 8, 2025
      If your Goodwe Inverter displays 'Fac Fail', it indicates a utility grid exception where the grid frequency change rate doesn't meet local standards. If this happens occasionally, the grid may be temporarily abnormal, and the inverter should recover automatically once the grid returns to normal. However, if it occurs frequently, verify that the grid frequency is within the permissible range. Contact your local power company if the grid frequency is outside of the allowed range. If the frequency is within range, contact your dealer or after-sales service for assistance.
  • E
    ericwolfeSep 5, 2025
    What should I do if my Goodwe Inverter shows 'DC Bus High'?
    • E
      ellisjoshuaSep 5, 2025
      If your Goodwe Inverter displays 'DC Bus High', it indicates an internal fault. Ensure that the software is the latest version. Restart the inverter to check if it begins to work properly.

Goodwe HT 73-136kW Series Specifications

General IconGeneral
Model SeriesHT 73-136kW Series
Max. DC Voltage1100 V
Rated AC Power73kW - 136kW
AC Voltage Range320 V - 480 V
Rated Grid Frequency50 Hz / 60 Hz
THDi< 3%
European Efficiency98.5%
Protection DegreeIP66
Ingress ProtectionIP66
CategoryInverter
Power Range73kW to 136kW
Nominal AC Voltage400V / 480V
Power Factor0.8 leading to 0.8 lagging
Cooling MethodSmart Air Cooling
CommunicationRS485, Ethernet, Wi-Fi