EasyManua.ls Logo

Goodwe HT Series - User Manual

Goodwe HT Series
59 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
User Manual
Grid-Tied PV Inverter
HT Series
(73-136kW)
V1.1-2022-07-20

Questions and Answers

  • A
    Anne MooreSep 18, 2025
    What causes 'PV Over Voltage' on a Goodwe HT Inverter and how to fix it?
    • B
      Brandi GarciaSep 18, 2025
      The 'PV Over Voltage' error on your Goodwe Inverter means that too many PV modules are connected in series, causing the open-circuit voltage to exceed the operating voltage. Check if the PV string input voltage matches the value displayed on the LCD. Also, verify that the PV string voltage meets the maximum input voltage requirements.
  • C
    Chloe TaylorAug 25, 2025
    How to fix an 'Over Temperature' error on a Goodwe HT?
    • C
      catherinetuckerAug 25, 2025
      If your Goodwe Inverter is showing an 'Over Temperature' error, it may be installed in a location with poor ventilation, the ambient temperature might be exceeding 60°C, or there could be a fault with the internal fan. Check the ventilation and ambient temperature around the installation point. If ventilation is poor or the temperature is too high, improve the ventilation and heat dissipation. If both are normal, it may indicate a need to contact support.
  • S
    stephaniejonesAug 25, 2025
    What causes a Vac Failure on a Goodwe Inverter?
    • C
      Cheyenne LewisAug 26, 2025
      A 'Vac Failure' on your Goodwe Inverter indicates that the utility grid voltage is outside the allowed range. To resolve this, ensure that the grid voltage is within the permissible limits and that the phase sequence of the AC cables are correctly connected, and the PE cable is properly and firmly connected.
  • R
    robertcardenasAug 27, 2025
    What does ISO Fail mean on a Goodwe Inverter?
    • L
      lovenicoleAug 27, 2025
      An 'ISO Fail' error on your Goodwe Inverter suggests that the PV system is short-circuited to the ground or is in a moist environment with poor insulation. Check the PV input cables for any breaks, ensure the module frames and metal bracket are securely grounded, and verify that the AC side is properly grounded.
  • L
    Lisa HintonSep 22, 2025
    What does 'Ground I Fail' mean on my Goodwe Inverter, and how can I resolve it?
    • L
      Lucas DavisSep 22, 2025
      The 'Ground I Fail' error on your Goodwe Inverter indicates that the input insulation impedance to the ground decreases during operation. Check if the inverter's working environment meets the requirements; for instance, high humidity on rainy days can cause this issue. Also, ensure that the components are properly grounded, and the AC side is correctly grounded.
  • J
    Jeremy HeathSep 23, 2025
    What does 'DC Bus High' mean on a Goodwe Inverter, and how do I fix it?
    • J
      Jonathan MartinSep 23, 2025
      The 'DC Bus High' error on your Goodwe Inverter usually indicates an internal fault. Make sure that the software is the latest version. Restart the inverter to check whether it can work properly.
  • B
    Brenda RobinsonSep 9, 2025
    What does 'Night BUS Fault' mean on my Goodwe Inverter?
    • J
      Jonathan HooperSep 10, 2025
      If your Goodwe Inverter displays the 'Night BUS Fault' message, it means there is a problem with the utility grid power or the AC cable is disconnected, or the AC breaker is off. To attempt a fix, disconnect the AC output switch and DC input switch, wait 5 minutes, then reconnect them. If the issue persists, contact your dealer or after-sales service.
  • P
    pcamachoSep 12, 2025
    What to do if my Goodwe HT Inverter displays 'DC-SPD'?
    • E
      Emily BridgesSep 12, 2025
      If your Goodwe Inverter shows 'DC-SPD', it indicates that the inverter was struck by lightning. As a first step, improve the lightning protection around the inverter. Then, disconnect the AC output switch and the DC input switch, wait 5 minutes, and reconnect them. If the problem continues after these steps, contact your dealer or after-sales service.
  • R
    Robert CrawfordSep 3, 2025
    What causes SPI Comm Fail on Goodwe HT?
    • R
      Robin CooleySep 3, 2025
      A 'SPI Comm Fail' error on your Goodwe Inverter could be due to the chip not being powered on or a wrong chip program version. Disconnect the AC output switch and DC input switch, then reconnect them after 5 minutes. If the problem persists, further assistance may be needed.
  • R
    Robert CohenSep 1, 2025
    What causes an ExFan Failure on a Goodwe Inverter?
    • A
      Amanda WadeSep 1, 2025
      An 'ExFan Failure' on your Goodwe Inverter can be due to an abnormal fan power supply, a mechanical issue, or the fan aging and becoming damaged. Disconnect the AC output switch and DC input switch, then connect them again after 5 minutes. If the problem continues, further assistance may be needed.

Summary

About This Manual

Applicable Model

Lists supported inverter models with their power and voltage ratings.

Target Audience

Specifies that the manual is for trained and knowledgeable technical professionals.

Symbol Definition

Explains the meaning of different hazard levels (Danger, Warning, Caution, Notice) used in the manual.

Updates

Lists version history and updates for the manual.

Safety Precaution

General Safety

Provides general safety guidelines and precautions for using the inverter.

DC Side

Details safety precautions related to the DC side of the inverter.

AC Side

Details safety precautions related to the AC side of the inverter.

Inverter Installation

Covers safety precautions specifically for the installation of the inverter.

Personal Requirements

Outlines the necessary qualifications and training for personnel handling the equipment.

Product Introduction

Application Scenarios

Describes the intended use of the HT inverter as a three-phase PV string grid-tied inverter.

Circuit Diagram

Presents the circuit diagrams for different HT inverter models.

Supported Grid Types

Illustrates the various grid structures (TN-S, TN-C, TT, IT) supported by the inverters.

Appearance

Details the physical components and layout of the inverter.

Check and Storage

Check Before Receiving

Lists items to check before accepting the product from the supplier.

Deliverables

Shows all the items included in the product package.

Storage

Provides guidelines for storing the inverter safely and appropriately.

Installation

Installation Requirements

Details environmental and location requirements for inverter installation.

Inverter Installation

Step-by-step guide for physically installing the inverter.

Electrical Connection

Safety Precautions

Essential safety rules to follow during electrical connections.

Connecting the PV Input Cable

Steps for connecting the DC input cables from the PV array.

Connecting the AC Output Cable

Guide for connecting the AC output power cable.

Communication

How to connect communication cables for data logging and monitoring.

Equipment Commissioning

Check Items Before Switching Power ON

Checklist of items to verify before powering on the inverter.

Power On

Step-by-step guide on how to safely power on the inverter.

System Commissioning

Indicators and Button

Explains the inverter's indicators and buttons for system status.

Setting Inverter Parameters via LCD

Guide for configuring inverter settings using the LCD interface.

Setting Inverter Parameters via App

Instructions for setting inverter parameters using a mobile application.

Monitoring via SEMS Portal

How to monitor inverter performance and status using the SEMS portal.

Maintenance

Power Off the Inverter

Steps to safely power off the inverter before performing maintenance.

Removing the Inverter

Procedures for safely detaching the inverter from its mounting.

Disposing of the Inverter

Guidelines for the proper disposal of the inverter according to regulations.

Troubleshooting

Common faults, their causes, and suggested solutions for the inverter.

Routine Maintenance

Schedule and methods for regular maintenance tasks.

Technical Parameters

Input

Specifications related to the inverter's DC input characteristics.

Output

Specifications related to the inverter's AC output characteristics.

Efficiency

Details on the maximum and European efficiency ratings of the inverter.

Protection

Lists various integrated and optional protection features of the inverter.

General Data

General specifications like temperature range, humidity, and altitude.

Goodwe HT Series Specifications

General IconGeneral
Max DC Input Voltage1100V
MPPT Voltage Range200-1000V
Max AC Output Power3.6kW to 10kW
Number of MPPTs1 or 2
Max PV Input Voltage1100V
MPPT Range200-1000V
AC Output Frequency50/60Hz
CommunicationRS485, Ethernet
Operating Temperature Range-25°C to 60°C
Protection LevelIP65