© copy right reserved by GoodWe
Utility Loss
Error Code: 23
Cause: Inverter detects no grid connected
Measurement:
A. Check if the AC switch is at ‘ON’ position, if not, please switch it on. If yes, please measure
the voltage of the AC connector and wiring of main switch board. Make sure the grid is on;
B. Check the L, N, PE are connecting to the right PIN. If not, please modify the wiring;
C. Check the ‘Vac’ displayed in the screen and the grid voltage, make sure the values are
within the limitation of the regulation. If not, please contact with your electrical company.
If yes, please contact with GoodWe local service center;
D. Switch of the AC & DC power of the inverter and wait for 5minutes. Measure the
impedance of L & N to ground, if the values are smaller than 200KΩ, please contact with
GoodWe local service center.
2.4 Trouble Shooting

Other manuals for Goodwe NS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe NS Series and is the answer not in the manual?

Goodwe NS Series Specifications

General IconGeneral
Protection DegreeIP65
Number of MPP Trackers2
CoolingNatural Convection
Power Range3kW to 6kW
MPPTDual MPPT
CommunicationWiFi
MPPT Voltage Range120-500V
Nominal AC Output Power3000W to 6000W
Max. AC Output Power3.3kW, 4kW, 4.6kW, 5.5kW, 6.6kW
Nominal Output Voltage230V
Operating Temperature Range-25 ~ +60 °C
Output Power3000W to 6000W
MPPT Range120-500V
Output Voltage230V
Frequency50/60 Hz

Related product manuals