PV Over Voltage Failure
Error Code: 17
Cause: DC input voltage is out of limitation
Measurement:
A. Check how many panels for each string, measure the Voc of the panel. If the values are
out of limitation, please modify the connection of PV string;
B. If the PV string is OK, please check the ‘Vpv’ displayed in the screen. If the values are not
the same, please contact with GoodWe local service center.
2.4 Trouble Shooting