Appendix G - Communications Gateway Module Installation Kit
3A2797ZAA 107
Data Exchange Interface Pointer Designation Table
Data Exchange
Pointer
Designation
Description Comments, Data Element Descriptions
Read/
Write
0 Interface Not Active ----- ---
1 Red Material Tank
Heat, Set point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
2 Read
3 Blue Material Tank
Heat, Set Point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
4 Read
5 Red Material Inline
Heater, Set point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
6 Read
7 Blue Material Inline
Heater, Set Point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
8 Read
9 Red Material Hose
Heat, Set point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
10 Read
11 Blue Material Hose
Heat, Set Point
temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
12 Read
13 Red Material Chiller
Temperature, Set
point temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
14 Read
15 Blue Material Chiller
Temperature, Set
Point temperature
Set or Get Set Point temperature, in 0.1 C
0
units.
Write
16 Read
80 -----
Current Zone Actual Temperature, in 0.1 C
o
units.
Read
82
Blue Material Tank
Zone, temperature
Current Zone Actual Temperature, in 0.1 C
o
units.
Read
84
Red Tank Blanket
Zone, temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
86
Blue Tank Blanket
Zone, temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
88
Red Material Inline
Heater Zone,
temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
90
Blue Material Inline
Heater Zone,
temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
92
Red Material Hose
Heat Zone,
temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
94
Blue Material Hose
Heat, temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read
96
Red Material Chiller
Zone, temperature
Current Zone Actual Temperature, in 0.1 C
o
units
Read