9.7.3 VIEW Menu Folder
‘VIEW’ folder displays the function or
status of the boiler.
To access the menu displays within
the ‘VIEW’ folder from the main burner
display, navigate as follows;
The ‘VIEW’ menu folder has 4 readout
displays as follows;
a. LUX %: Light illumination
measured by the Photocell.
Readout is instantaneous.
b. STEP AUTO: Each boiler function
is allocated a two digit number.
This menu displays the function
the boiler is in when viewing. The
list of the functions are as follows:
03 - Wait Boiler Thermostat
13 - Pellet Burner Firing
14 - Turning Off Brazier
15 - Brazier is moving back
15 - Brazier is moving forward
26 - Post Purge
29 - Air Pressure Error
33 - Failed Pellet Lighting
34 - Servo Motor Blocked
40 - Pre-load
41 - Wait Lighting (Ignition)
42 - Wait Lighting (Lighting Feed Reduced)
45 - Wait Lighting (Flame Stabilisation)
47 - Probe Fault
c. VIEW CLE BRAZ Total pellet feed
auger run time since brazier last
cleaned. When ≥ 180 Min brazier
cleaning operation will commence.
Resets after each brazier clean.
d. VIEW CLE BOILER Total pellet
feed auger run time since boiler
last cleaned. When ≥ ‘180 Min
boiler cleaning operation will
commence. Resets after each
boiler clean.
9.7.4 USER Menu Folder
‘USER’ folder; allows the user change
the language on the burner display.
To access the menu displays within
the ‘USER’ folder from the main burner
display, navigate as follows;
The language options are Italian or
English. Once exited, the language
selection shown on screen becomes
the displayed language.