21
Parameter
Meaning
Range
Default
Remarks
1
To set the entering water
temp. under heating mode
15-42°C
28°C
Adjustable
2
Entry into defrosting time
period
30-90MIN
40MIN
Adjustable
3
Terms of Entry defrosting
function
-30°C to0°C
-7°C
Adjustable
4
Terms of Exit defrosting
2 to 30°C
20°C
Adjustable
5
Time of Exit defrosting
1 to 12MIN
12MIN
Adjustable
6
Mode: 0 Heat
0
0
Not adjustable
7
Mode selection of Electronic
expansion valve
0-1
1(auto)
Adjustable
A
Manual adjustment steps of
electronic expansion valve
18-94
70
Adjustable
L
Entering water temperature
calibration
-9.9-9.9
0
Adjustable
Recover to Factory default setting
Long press and simultaneously in 10 second to recover to factory default setting ,it will display 0000”
and then back to “OFF”.