EasyManua.ls Logo

Gree FB01 - Requirements on Water System and Water Quality; Trial Run

Gree FB01
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D Series Modular Air-cooled Scroll Chillers
34
(3) Close the main power switch.
(4) Check if the voltage between terminals keeps balance within deviation of 2%.
(5) Check if the power consumption of the unit complies with the rated value on the nameplate.
(6) Be sure the power cord is capable of carrying the rated current on the nameplate.
(7) Be sure all valves of water and refrigerant pipeline are placed properly.
(8) Reset all hand reset control elements.
(9) Be sure all sensor are placed installed properly.
7.2 Requirements on Water System and Water Quality
Be sure to open the water pump after the water system has been ushed times and the water quality
has met the requirements and meanwhile be sure the water ow rate and pressure are within the allowable
range.
The industrial water generates little scale when used as the refrigeration medium while the well or river
water will generate much more scale and sands which would reduce the ow rate of the evaporate and
cause freezing. Therefore, the well or river water must be rstly treated with the water softening equipment
and analyze the PH, heat conductivity, Cl ion, and S ion before use.
Water Quality Requirement
Items
Chilled water Potential effect
Circulating water
(<20
)
Supply water Corrosion Scale
PH 6.5~8.0 6.5~8.0
Heat Conductivity <200uV/cm(25
) <200uV/cm(25
)
Cl ion <50ppm <50ppm
SO
4
ion <50ppm <50ppm
Fe <1ppm <0.3ppm
Basic ion <50ppm <50ppm
Hardness <50ppm
<50ppm
S ion / /
Amonia ion / /
Si <30ppm <30ppm
Na ion / /
NOTE: “○” indicate possible corrosion or scale.
Even if the water qualify is under the strict control, calcium dioxide or other minerals will still form on the
surface of the heat exchanger which will affect the heat exchange efciency and be eliminated by formic
acid, lemon acid, acetic acid or other organic acid.
7.3 Trial Run
See the operation manual of the applicable controller for more details.
(1) When the unit has not been used for a long period or the ambient temperature is quiet low, keep the
unit energized 8 hours before startup to preheat the crankcase of the compressor so as evaporate
the liquid refrigerant inside the compressor which otherwise would cause adverse effect on the
compressor.
(2) Be sure valves are opened properly to prevent the compressor from being damaged by the abnormal
high pressure.
(3) Carefully adjust the ow control valve and the shutoff valve of the chilled water system to make the
ow rate meet the rated value on the nameplate.

Related product manuals