GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
108
1.3.3 Function Setting Operations
Step 1: Open the commissioning window of the master unit panel.
Step 2: Power on the entire unit.
Step 3: Press "SW3" on the master unit to enter the to-be-selected status of function settings. By
default, the master unit is displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress
Display Mode
Current Status
Display Mode
A7
Blinking
00
Blinking
00
Blinking
Users can select corresponding functions by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master
unit, including:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress
Display Mode
Current Status
Display Mode
A7
Blinking
00
Blinking
00
Blinking
A6
Blinking
00
Blinking
00
Blinking
A2
Blinking
00
Blinking
00
Blinking
A8
Blinking
00
Blinking
00
Blinking
n0
Blinking
01
Blinking
00
Blinking
n3
Blinking
00
Blinking
00
Blinking
n4
Blinking
00
Blinking
00
Blinking
n5
Blinking
00
Blinking
00
Blinking
After selecting the functions to be set, press "SW7" to confirm entering function settings. The master
unit is displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress
Display Mode
Current Status
Display Mode
A7
On
00
Blinking
OC
Blinking
A6
On
nC
Blinking
nC
Blinking
A2
On
01
Blinking
00
Blinking
A8
On
00
Blinking
OC
Blinking
n0
On
01
Blinking
OC
Blinking
n3
On
00
Blinking
00
Blinking
n4
On
10
Blinking
OC
Blinking
n5
On
00
Blinking
OC
Blinking
Then go to step 4 to set corresponding functions.
Step 4: Set function parameters.
Setting methods of function parameters are as follows:
(1) A7 Outdoor silent mode settings
Step 1: Confirm entering the A7 outdoor silent mode settings. The master unit is displayed as