GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
12
4 BASIC PARAMETERS OF UNIT
Outdoor Units_Heat Pump
-
6Ton
8Ton
10Ton
Horse Power
HP
8
10
12
Model
-
GMV-72WM/B-F(U)
GMV-96WM/B-F(U)
GMV-120WM/B-F(U)
Module combination
-
GMV-72WM/B-F(U)
GMV-96WM/B-F(U)
GMV-120WM/B-F(U)
Power Supply
-
208/230V 3~60Hz
208/230V 3~60Hz
208/230V 3~60Hz
Code
-
CN851W1380
CN851W1390
CN851W1420
Compr
essor
Type
-
Inverter scroll type
Inverter scroll type
Inverter scroll type
Number
N
1
1
2
Refrigeration Oil Brand
-
FVC68D or FV-68H
FVC68D or FV-68H
FVC68D or FV-68H
Oil Charge
â‘ 
Total
L
4
4
5.5
Compresso
r
L
1
1
1×2
Oil
Banlance
Tank
L
3
3
3.5
Pipe
Conne
ction
Gas Pipe Size
mm
19.05
22.2
28.6
in.
3/4
7/8
1 1/8
Liquid Pipe Size
mm
9.52
9.52
12.7
in.
3/8
3/8
1/2
Oil Balance Pipe Size
mm
9.52
9.52
9.52
in.
3/8
3/8
3/8
Dimen
sions
(width
×depth
×heigh
t)
External Dimension
mm
930×765×1605
1340×765×1605
1340×765×1605
in.
36-3/5×30-1/8×63-1/
5
52-3/4×30-1/8×63-1/
5
52-3/4×30-1/8×63-1/
5
Weight
Net Weight
kg
225
300
360
lbs.
496
661
794
Maximum qty of connected indoor units
unit
12
16
20
Remark
Oil charge includes the total oil amount of outdoor units, residual
oil amount of compressor and oil balance tank. When replacing the
compressor or oil balance tank, only the corresponding required oil
amount shall be charged

Table of Contents

Other manuals for Gree GMV-120WM/B-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-120WM/B-F and is the answer not in the manual?

Gree GMV-120WM/B-F Specifications

General IconGeneral
BrandGree
ModelGMV-120WM/B-F
CategoryInverter
LanguageEnglish

Related product manuals